Herunterladen Inhalt Inhalt Diese Seite drucken

SICK S3000 Expert Bedienungsanleitung Seite 130

Sicherheits-laserscanner
Inhaltsverzeichnis

Werbung

Block description
Data block name
Online output trigger
config block
130
© SICK AG • Industrial Safety Systems • Germany • All rights reserved
12.2.7
Online output trigger config block (block no. 105)
This block is used to change the content of the CMS telegram online.
Changes are volatile, i. e. they are not maintained through power down.
Block no.
105
Register description
Register name
Block word
Output trigger
0
configuration
Block size
External access
2 Byte
Read
Write
Field bits
Field name
0 ... 1
Trigger
condition
2
Control area A
3
n/u
4
Reflector
detected
5
Device glared
6
Field
evaluation A
7
Field
evaluation B
8
Field
evaluation C
9
Field
evaluation D
10 ... 15
n/u
Telegram Listing CMS
S3000/S300 Expert
Field description
0: No data output
1: Continuous output
2: Internal event
(Shall only be different to
"0" if allowed by device
capabilities.)
Triggers on detected
objects within protective or
warning field.
n/u
Triggers on detected
reflector.
Triggers on detected glare
in distance measurement.
Triggers on detected
object in field A.
Triggers on detected
object in field B.
Triggers on detected
object in field C.
Triggers on detected
object in field D.
n/u
8015791/WS20/2012-12-12
Subject to change without notice

Werbung

Kapitel

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

S300 expert

Inhaltsverzeichnis