Commissioning
7.2
Switching on the transmitter
Switch on the supply voltage after completing the final checks. The device is ready for
operation after approx. 20 seconds! The transmitter performs a number of internal test
functions after power-up. As this procedure progresses, the following sequence of messages
appears on the local display:
Step
Display
1
All segments on
2
All segments off
3
Manufacturer data and device name are displayed
4
Current firmware version is displayed
5
Current device revision is displayed
6a
The current measured value is displayed. Bar graph displays the % value within the set bar graph range
6b
The current status message is displayed. If the switch-on procedure fails, the appropriate status message is
displayed, depending on the cause.
If the switch-on procedure is not successful, the relevant diagnostics event, depending on the cause, is
displayed. A detailed list of diagnostic events and the corresponding troubleshooting instructions can
be found in the Operating Instructions.
Normal measuring mode commences as soon as the switch-on procedure is completed.
Various measured value and/or status variables appear on the display.
52
iTEMP TMT162
Endress+Hauser