Wiring
4.4
Post-installation check
After installing the device, always run the following final checks:
Device condition and specifications
Is the device undamaged (visual inspection)?
Do the ambient conditions match the device specification (e.g. ambient temperature, etc.)?
5
Wiring
5.1
Connection conditions
CAUTION
L
The electronics could be destroyed
Switch off power supply before installing or connecting the device. Failure to observe this
may result in destruction of parts of the electronics.
When installing Ex-approved devices in a hazardous area please take special note of the
instructions and connection schematics in the respective Ex documentation added to these
Operating Instructions. Your supplier is available for assistance if required.
A Phillips head screwdriver is required to wire the field transmitter at the terminals.
NOTICE
Do not overtighten the screw terminals, as this could damage the transmitter.
Maximum torque = 1 Nm (³⁄₄ lbf ft).
For wiring the device proceed as follows:
1.
Remove the cover clamp. →  41
2.
Unscrew the housing cover on the connection compartment together with the O-ring.
→  41
3.
Open the cable glands of the device.
4.
Route the appropriate connecting cables through the openings of the cable glands.
5.
Connect the cables as indicated →  20,  43 as well as in the sections: Connecting
the sensor →  43and Connecting the measuring device. →  44
On completion of the wiring, screw the screw terminals tight. Tighten the cable glands again.
Refer to the information provided in the ' E nsuring the degree of protection' section. Screw the
housing cover tight again and fit the cover clamp back on. →  41
In order to avoid connection errors always follow the instructions in the post-connection check
section before commissioning!