Herunterladen Diese Seite drucken

Endress+Hauser iTEMP TMT162 Kurzanleitung Seite 46

Vorschau ausblenden Andere Handbücher für iTEMP TMT162:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Wiring
tightened, the Iris spring is pressed against the shielding, thereby creating a conductive
connection between the shielding and the metal housing.
A connection box or a plug-in connection is to be seen as part of the shielding (Faraday
shield). This applies, in particular, to remote boxes if these are connected to a FOUNDATION
Fieldbus device by means of a pluggable cable. In such instances, a metallic connector must be
used where the cable shielding is positioned at the plug housing (e.g. prefabricated cables).
1
1.1
1.2
 22
Connectors for connecting to the FOUNDATION Fieldbus
1
Connectors on housing (male - pin assignment/color codes):
1.1 Blue wire: FF- (terminal 2)
1.2 Brown wire FF+ (terminal 2)
1.3 Gray wire: shield
1.4 Green-yellow wire: ground
1.5 Positioning key
2
7/8" UNC thread
3
Fieldbus connector
4
Field housing
Connector technical data:
Wire cross-section
Connection thread
Degree of protection
Contact plating
Housing material
Flammability
46
1.3
2
1.4
1.5
2
4 x 0.8 mm
M20 x 1.5 / ½" NPT
IP 67 according to DIN 40 050 IEC 529
CuZn, gold-plated
1.4401 (316)
V - 2 according to UL - 94
3
SW/AF 26
iTEMP TMT162
4
M20x1.5/
½" NPT
Endress+Hauser