Functional Description
These parameters are used to set and verify the IO Option configuration. If the status parameter is not OK then the drive will not enter the
Operational state.
Status
Description
OK
The configuration is valid. The status will always be OK if no IO option is required, even if one is fitted. Alternatively, if
the IO option fitted is working correctly and supports the required functionality then the status will be OK
For example, if the required type is THERMISTOR and the actual type is GENERAL PURPOSE then the status will
be OK as the General Purpose option supports the thermistor functionality.
OPTION NOT FITTED
An option was required and none was detected
TYPE MISMATCH
The fitted option does not support the required features
TYPE UNKNOWN
The firmware in the drive does not recognise the fitted option
HARDWARE FAULT
The fitted option is not working as expected.