Herunterladen Inhalt Inhalt Diese Seite drucken

Parker AC30E Produkthandbuch Seite 334

Ac30-baureihe
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

D-48
Parameter Reference
DC Link Volts Limit
Parameters::Motor Control::DC Link Volts Limit
This function prevents over-voltage faults occurring due to a rapidly changing setpoint.
Parameter Name
No.
VDC Lim Enable
1641
Enable DC Link Volts Limit during a fast deceleration to prevent overvoltage trip
VDC Lim Level
1642
Determines the dc link volts at which the DC Link Volts Limit sequence is started.
Entered as a percentage of the max DC link voltage (drive overvoltage level = 100%).
VDC Lim Active
1643
Set True when the deceleration ramp is paused in order to limit the DC link voltage
VDC Lim Output
1644
This diagnostic represents the speed setpoint output of the DC Link Volts limit Feature in Electrical Hz
Path
Parameters::Motor Control::DC Link
Volts Limit
Parameters::Motor Control::DC Link
Volts Limit
Parameters::Motor Control::DC Link
Volts Limit
Parameters::Motor Control::DC Link
Volts Limit
Default
Range
FALSE
91.0
78.0 to 100.0
x.x
Min to Max
Units
Writable
STOPPED
STOPPED
%
NEVER
Hz
NEVER
AC30 series Variable Speed Drive

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Ac30fAc30k ac30pAc30dAc30gAc30hAc30j

Inhaltsverzeichnis