Herunterladen Diese Seite drucken

TR-Electronic CMV582M 8192/4096 EPN 36ZB10FL Serie Gesamt-Bedienungsanleitung Seite 195

Werbung

8.3.4.7.6 Profile identification (PNU 965)
This parameter contains the encoder profile identification number that identifies the profile (0x3D) and
the profile version (4.1 or 4.2).
PNU
965
Meaning
Profile identification
Data type
OctetString 2 (Unsigned16)
Access
read
Byte
Data
8.3.4.7.7 Parameter storage (permanent) (PNU 971)
Use this parameter to save the currently set parameter values in the non-volatile memory (RAM Data).
After saving, the parameter value of PNU 971 is automatically reset to 0.
The parameter control PNU 65005 must be set accordingly for the stored parameters to be loaded
from the non-volatile memory at the next startup of the measuring system, see Chapter 8.3.4.4 on
Page 136.
PNU
971
Meaning
Saving the parameters to the non-volatile memory
Data type
Unsigned16
Access
read/write
Activation
with write access
Default value
0x0000
Permitted values
0x0001: save current parameter values to non-volatile memory
8.3.4.7.8 Device RESET / parameter activation (PNU 972)
Use this parameter to force a device RESET, e.g. during the commissioning phase, when all
parameters have been set and the measuring system has to be reinitialized or after elimination of
errors to delete an error message.
Printed in the Federal Republic of Germany
07/21/2022
Profile no.
1
61 (0x3D)
Danger of physical injury and material damage due to uncontrolled
movements of the drive system when executing the RESET function!
 The measuring system immediately stops communicating when a RESET
command is received; this can result in uncontrolled system conditions.
Therefore, the application must be transferred to a safe state before the
RESET command is executed. The write protection for this parameter
prevents unwanted access, see Chapter 8.3.4.4 on Page 136.
TR-ECE-BA-DGB-0132 v21
Profile version
2
41 (0x29) / 42 (0x2A)
 TR-Electronic GmbH 2017, All Rights Reserved
Page 139 of 168

Werbung

loading