9.2.2 Base settings for process control
Type of base setting
(observe sequence)
1. Set the safety position
2. Select physical unit for process
control
3. Configure process values
a) Select standard signal for
process set-point value
b) Scale process set-point value
c) Select standard signal for
process actual value
d) Scale process actual value
4. Scaling the process control
5. Set dead band for process control
6. Position control adjustment
AG2: see chapter "9.4"
AG3: see chapter "9.5"
40
Factory default setting
Close
Per cent
Signal type analogue:
4...20 mA
Gateway: Specified by fieldbus
Minimum 0%, maximum 100%
4...20 mA
Minimum 0%, maximum 100%
Minimum 0%, maximum 100%
1%
-
english
Type 3363, 3364, 3365
Start-up
Type of base setting
(observe sequence)
7. Set up process control
a) Linearising process characte-
1)
ristic
(function P.LIN)
Additionally for devices without
display: set DIP switch 2 to
ON to activate the correction
characteristic.
b) Adjust process control
(P.TUNE function)
8.
Set AUTOMATIC operating state
Tab. 19: Overview: base settings for process control
1) Only necessary if process characteristic varies substantially from line-
arity. Linearisation using the function P.LIN can take a lot of time with
slow processes.
2) The P.TUNE function supports process control set-up by indepen-
dently optimising process parameters.
The process of fine-tuning process parameters is described in the Type
3363 software description.