Herunterladen Inhalt Inhalt Diese Seite drucken

Energy Meter - Parker AC30P Handbuch

Ac30-serie
Vorschau ausblenden Andere Handbücher für AC30P:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Energy Meter

Monitor::Energy Meter
Parameters::Motor Control::Energy Meter
This feature measures the electrical energy used by the motor.
Parameter Name
No.
Power kW
0380
This diagnostic shows the power being delivered to the load in kilowatts.
Power HP
0381
This diagnostic shows the power being delivered to the load in horsepower.
Reactive Power
0382
This diagnostic shows the reactive power being delivered to the load in kilo volt-amperes reactive.
Energy kWh
0383
This diagnostic shows the total energy consumed by the load in kilowatt hours.
Power Factor Est
0385
This diagnostic shows the power factor estimate (between 0 and 1).
0386
Power Factor Angle Est
This diagnostic shows the power factor angle estimate.
AC30 series Variable Speed Drive
Path
Monitor::Energy Meter
Parameters::Motor Control::Energy
Meter
Same as PNO 380
Same as PNO 380
Same as PNO 380
Same as PNO 380
Parameters::Motor Control::Energy
Meter
Parameter Reference
Default
Range
x.xx
0.00 to 1000000.00
x.xx
0.00 to 1000000.00
x.xx
0.00 to 1000000.00
x.xx
0.00 to 10000000.00
x.xx
0.00 to 1.00
x.xx
0.00 to 90.00
D-59
Units
Writable
kW
NEVER
NEVER
HP
kVAr
NEVER
kWh
NEVER
NEVER
deg
NEVER

Werbung