The Auto Restart feature provides the facility to automatically reset a choice of trip events and restart the drive with a programmed number of
attempts. The number of attempted restarts is monitored. A manual or remote trip reset is required if the drive is not successfully restarted within the
maximum number of restarts. The purpose of this feature is to allow automatic recovery from trip conditions. This is especially useful on remote or
unmonitored sites.
Parameter Name
No.
AR Enable
1469
Enables the auto restart function.
AR Mode
1470
Defines the action that the AR function will take following a trip.
0.
TRIP RESET
1.
AUTO RESTART
2.
AUTO START
Refer to the Functional Description below for more details.
AR Max Restarts
1471
Defines the maximum number of restart attempts permitted before the AR function disables itself.
AC30 series Variable Speed Drive
Path
Setup::Motor Control::Auto Restart
Parameters::Motor Control::Auto Restart
Same as PNO 1469
Trips will be reset when the trip sources are inactive. The drive will not be restarted.
If it was running the drive will be restarted when the trip sources are inactive and run is active.
The drive will be started when the trip sources are inactive if the run signal is high