Linear encoder

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

4.4 Setting the Node-ID and Baud rate by means of LMT services
4.4.1 Configuration of the Node-ID, sequence
Default setting: Node-ID = 127 dec.
Assumption:
-
-
-
Procedure:
4.4.2 Configuration of the Baud rate, sequence
Default setting: Baud rate = 500 kbit/s
Assumption:
-
-
-
Procedure:
Printed in the Federal Republic of Germany
02/23/2022
LMT address unknown
only one LMT slave should be in the network
the Node-ID 12 dec. shall be adjusted
Perform service 04 Switch mode global protocol,
Mode = 1, to switch the LMT slave into Configuration Mode.
Perform service 17 Configure NMT-address protocol, Node-ID = 12.
--> Wait for acknowledgement and check successfully execution,
--> Error Code = 0.
Perform service 23 Store configuration protocol.
--> Wait for acknowledgement and check successfully execution,
--> Error Code = 0.
--> LMT slave is reset and is in condition PRE-OPERATIONAL.
LMT address unknown
only one LMT slave should be in the network
the Baud rate 125 kbit/s shall be adjusted
Perform service 04 Switch mode global protocol,
Mode = 1, to switch the LMT slave into Configuration Mode.
Perform service 19 Configure bit timing parameters protocol,
Table Selector = 0, Table Index = 4
--> Wait for acknowledgement and check successfully execution,
--> Error Code = 0.
Perform service 23 Store configuration protocol.
--> Wait for acknowledgement and check successfully execution,
--> Error Code = 0.
--> LMT slave is reset and is in condition PRE-OPERATIONAL.
TR-ELA-BA-DGB-0024 v06
 TR-Electronic GmbH 2015, All Rights Reserved
Page 125 of 155