Code
Warning
570
Electronic module too
hot.
Additional information about causes and remedies:
The electronic module must adjust the pump's operation in the event of notice-
able overheating
to prevent damage to electronic components.
571
Twin-head pump con-
nection interrupted.
Additional information about causes and remedy:
Pump function slightly impaired. The motor head meets the pump function up to
the performance limit.
See also additional information for code 582.
573
Communication to dis-
play and operating unit
interrupted.
Additional information about causes and remedies:
The display and operating unit is connected to the pump's electronics on its rear
side via a ribbon cable.
574
Communication to CIF
module interrupted.
Additional information about causes and remedy:
The CIF module is connected to the pump in the terminal room via four contacts.
578
Display and control unit
defective.
Additional information about causes and remedy:
The display and operating unit is available as a spare part.
582
Twin-head pump is not
compatible.
Additional information about causes and remedy:
Twin-head pump function is only possible with two compatible pumps of the
same type.
Check the compatibility of the software versions of both twin-head pump part-
ners.
Contact service.
586
Overvoltage
Additional information about causes and remedy:
The pump is running. If the voltage continues to increase, the pump is shut
down.
Excessive voltages can damage the pump.
588
Electronic fan blocked,
defective or not connec-
ted.
1)
BMS = Building management system
NOTICE
The warning W573 "Communication to the display and control unit in-
terrupted", is shown differently from all other warnings on the display.
Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.01/2023-03
Cause
Remedy
Critical temperature of
Ensure permissible ambient
the electronic module
temperature. Improve room
exceeded.
ventilation.
The connection to the
Check power supply of the
twin-head pump part-
twin-head pump partner,
ner cannot be made.
cable connection and con-
figuration.
Internal communica-
Check the ribbon cable con-
tion to display and op-
nection.
erating unit interrup-
ted.
Internal communica-
Check/clean contacts
tion to the CIF module
between CIF module and
interrupted.
electronic module.
A fault in the display
Replace display and operat-
and operating unit has
ing unit.
been identified.
Twin-head pump
Select/install appropriate
partner is not compat-
twin-head pump partner.
ible with this pump.
Power supply is too
Check power supply
high.
Electronic fan does not
Check the fan cable.
work