Magnetic field positioning system
8
IO-Link interface (continued)

8.5.10 Data storage

Index
Subindex Name
Data Storage
1
0x0003 (3)
2
3
4
5
Tab. 8-13: Data storage parameter

8.5.11 Access locks (Device Access Locks)

With this standard parameter, it is possible to activate or
deactivate certain functions of the IO-Link device.
With the BMP 01-..., there is the option to lock the function
of the parameter manager and the button. To do so, the
respective bit of the 2-byte value must be set to 1 (locked).
In order to unlock the function again, the bit is set to 0.
Bit 0
Lock parameter access
(not supported)
Bit 1
Lock parameter management
(supported)
Bit 2
Locking the button
(supported)
Bit 3
Lock local user interface
(not supported)
Bit 4...15
reserved
Tab. 8-14: Lock parameter data

8.5.12 Profiles and functions (ProfileCharacteristic)

This parameter indicates which profile is supported by the
IO-Link device.
Subindex 1 (DeviceProfileID):
0×000B (Measuring Sensor, high resolution according
to Smart Sensor Profile Edition 2)
Subindex 2 (DeviceProfileID):
0×4000 (Identification and Diagnosis according to
Common Profile)
Subindex 3 (FunctionClassID):
0×8001 (SSC Function Class)
Subindex 4 (FunctionClassID):
0×8004 (Teach Channel)
www.balluff.com
Size
Command
1 byte
State Property
1 byte
Size
4 bytes
Parameter Checksum
4 bytes
Index List
62 bytes
Access
Values
Read/Write
The Data Storage parameter is needed by
Read Only
the IO-Link master for the data storage
Read Only
function. This parameter cannot be user
modified.
Read Only
Read Only

8.5.13 Process data structure (PD Input Descriptor)

This parameter describes the composition of the process
data used.
Each part of the process data is written with 3 bytes.
Subindex Values
0x01
1
0x08
0x00
0x03
2
0x08
0x08
0x03
3
0x20
0x10
Tab. 8-15: Process data structure
Subindex 0 can be used to read out the complete process
data description (see Section Process data (PD) on
page 20).
Description
Boolean set
8-bit length
0-bit offset
Signed Integer
8-bit length
8-bit offset
Signed Integer
32-bit length
16-bit offset
english