Herunterladen Inhalt Inhalt Diese Seite drucken

HBM WE2108 Serie Referenzhandbuch Seite 128

Teil 2
Vorschau ausblenden Andere Handbücher für WE2108 Serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

128
(limit value refresh)
Description:
This command activates the limit values that were entered using LIV, without writing on the
EEPROM. This command should be used for applications with frequently changing set
points, because the EEPROM memory only provides a limited number of write cycles.
After restart, the limit values last stored using TDD1 will be effective.
(Measurement status)
Output of the measurement status according to the below table
Output of an 8−bit value which has the following meaning:
Bit 0...7
0
1
2
3
4
5
6
7
HBM
LVR
Command:
Query:
Password protection: no
Parameter backup:
MST
Command:
Query:
Parameter:
Password protection: no
Parameter backup:
Meaning
1 = Gross value outside display limits
0 = Gross
1 = Net
1 = Precise zero (measured value < 1/4d)
1 = Standstill
1 = Limit value1 active
1 = Limit value2 active
With two−range/two−division scale:
0 = scale within range 1
1 = scale within range 2
With counting scale:
0 = Weight display
1 = Counter display
0 = Error (ErrXX displayed)
1 = no error
LVR;
not available
no
not available
MST?;
−−
−−
Scale electronic unit (NSW)
WE2108

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

We2108sWe2108m

Inhaltsverzeichnis