7. Configuration without display and operating unit

7. Configuration without display and operating unit

7.1 Performing a mounting correction (offset)

The mounting correction corrects a zero offset in the output signal by defining a new
zero point. The zero offset is caused by the mounting position.
Correction range: ±20 % of maximum measuring range
Required tool: Multimeter (ammeter)
1. Screw off the case head cover and pull out the push-on cap.
2. Press [Zero] for approx. 2 s (e.g. with measuring tip of a multimeter).
» Mounting correction successful: Control diode lights up for 2 s.
» Mounting correction unsuccessful: Control diode blinks 5 times.
3. Check the output signal as follows.
CAUTION!
Incorrect connection
A short-circuit will destroy the process transmitter.
Ensure that the multimeter does not come into contact with the positi-
ve power supply terminal.
Set the multimeter to current measurement.
Connect the positive measuring line of the multimeter to the test contact.
Connect the negative measuring line of the multimeter to the negative power
supply terminal.
» The result of the current measurement should give a value between 4 ... 20 mA
in the pressure-free condition. If the ambient atmospheric pressure is outside
the measuring range, the measured current can be < 4 mA or > 20mA.
WIKA operating instructions, process transmitter, model UPT-2x
Control diode
Mounting correction, [Zero] key
Test contact
Positive power supply terminal +
Negative power supply terminal –