5. Commissioning, operation
5.2.2 Requirements for connection cable
Use and assemble connection cable that is suitable for the application. For cables
■
with flexible wires, always use ferrules appropriate for the wire cross-section.
Where there is electromagnetic radiation above the test values per EN 61326, a
■
shielded connection cable must be used.
When using an M12 x 1 (4-pin) circular connector, the mating connector is supplied
■
by the customer. Ensure the matching design from the connector manufacturer.
Electrical connections
Cable gland M20 x 1.5 and spring-loaded
terminals
Angular connector DIN 175301-803A with
mating connector
Circular connector M12 x 1 (4-pin) without
mating connector
Ground screw, inside
Ground screw, outside
WIKA operating instructions, process transmitter, model UPT-2x
Ingress protection: IP66/67
Cable diameter: 5 ... 12 mm
Wire cross-section: max. 2.5 mm
Single cable: 0.13 ... 2.5 mm²
End splices: 0.13 ... 1.5 mm²
For cable diameters outside of 5 ... 12 mm, change
the seal and cable gland
Ingress protection: IP65
Cable diameter: 6 ... 8 mm
Wire cross-section: max. 1.5 mm²
Ingress protection: IP65
Observe manufacturer's specifications
0.13 ... 2.5 mm²
0.13 ... 4 mm²
(AWG 14)
2
15