9. Diagnostic functions
9. Diagnostic functions
Requirement: Display and operating unit fitted.
9.1
Simulations
9.1.1
Performing a pressure simulation
A pressure value within the measuring range must be entered and is converted into a
current value and output.
1. Open the operating menu with [↵].
Select "Diagnostic" and confirm with [↵].
2. Select "Simulation" and confirm with [↵].
3. Select "Press. simu." and confirm with [↵].
4. Change digit using [▲] [▼] and confirm with [↵]. The cursor
moves to the next digit. Repeat for each digit.
» Simulation is active.
5. Ending the simulation. Press [ESC] to do this.
9.1.2
Performing a current simulation
The selected or entered current value will be simulated and output as the PV (primary
value).
1. Open the operating menu with [↵].
Select "Diagnostic" and confirm with [↵].
2. Select "Simulation" and confirm with [↵].
3. Select "Current sim." and confirm with [↵].
4. Select the current value or define via "Input".
Change digit using [▲] [▼] and confirm with [↵]. The cursor
moves to the next digit. Repeat for each digit.
» Simulation is active.
5. Ending the simulation. Press [ESC] to do this.
WIKA operating instructions, process transmitter, model UPT-2x