5. Commissioning, operation

5.3 Electrical connection

The electrical connection must only be made by qualified skilled
personnel.
Wire the reed sensor in accordance with the connection diagram of
the electrical output (see product label). The connection terminals are
appropriately marked.
Electrical output
3-wire potentiometer
circuit
Head-mounted transmitter
with 4 ... 20 mA
Seal the cable bushing  at the connection housing .
WARNING!
Malfunctions through voltage spikes due to running cables
together with mains connection leads or due to large cable
lengths.
This can lead to a malfunction in the plant and thus lead to
injury to personnel or damage to equipment.
Use shielded connection leads
Ground connection leads at one end
Always observe the mounting and operating instructions of accessories
when commissioning them.
Operating instructions reed sensor, model BLR

Connection diagram

BU/GY
BN
BK
+
R
I
4 ... 20 mA
A
DC 12 ... 30 V