8. Configuration without display and operating unit
All manuals and user guides at all-guides.com
8. Configuration without display and operating unit
8.1 Performing a mounting correction (offset)
The mounting correction corrects a zero offset in the output signal by defining a new
zero point. The zero offset is caused by the mounting position.
Correction range: ±20 % of maximum measuring range
Required tool: Multimeter (ammeter)
1. Screw off the case head cover and pull out the push-on cap.
2. Press [Zero] for approx. 2 s (e.g. with measuring tip of a multimeter).
Mounting correction successful: Control diode lights up for 2 s.
Mounting correction unsuccessful: Control diode blinks 5 times.
3. Check the output signal as follows.
CAUTION!
Incorrect connection.
A short circuit will destroy the process transmitter.
- Ensure that the multimeter does not come into contact with the positive
power supply terminal.
Set the multimeter to current measurement.
■
Connect the positive measuring line of the multimeter to the test contact.
■
Connect the negative measuring line of the multimeter to the negative power
■
supply terminal.
WIKA operating instructions process transmitter, model UPT-2x
Control diode
Mounting correction, [Zero] key
Test contact
Positive power supply terminal +
Negative power supply terminal –