9.1 Object 2000h: Accept parameters
With write access to this object, the measuring system accepts the parameters in the
non-volatile memory (EEPROM).
Index
Description
Data type
Category
Access
PDO mapping
Value
9.2 Scaling parameter
With the scaling parameters the physical resolution of the measuring system can be
changed. The position value output is binary decoded and is calculated with a zero
point correction and the count direction set. The measuring system does not support
decimal numbers in this configuration or numbers of revolutions (gearbox function)
deviating from exponents of 2.
9.2.1 Object 2001h: Number of Revolutions / -numerator
Defines the number of revolutions of the measuring system before the measuring
system restarts at zero.
Index
Description
Data type
Category
Access
PDO mapping
Lower limit
Upper limit
Default
Printed in the Federal Republic of Germany
10/21/2014
0x2000
Accept Parameters
UNSIGNED32
Optional
rw
No
Not relevant
0x2001
Number of Revolutions / -numerator
UNSIGNED32
Mandatory
rw
No
1 revolution
32768 revolutions (Max. value see nameplate)
4096
TR - ECE - BA - DGB - 0069 - 06