FB 10 AWL
NAME :UHR-STEL
BEZ
:SCHJ
E/A/D/B/T/Z: E
BEZ
:WOTG
E/A/D/B/T/Z: E
BEZ
:TAG
E/A/D/B/T/Z: E
BEZ
:MON
E/A/D/B/T/Z: E
BEZ
:JAHR
E/A/D/B/T/Z: E
BEZ
:STD
E/A/D/B/T/Z: E
BEZ
:AMPM
E/A/D/B/T/Z: E
BEZ
:MIN
E/A/D/B/T/Z: E
BEZ
:SEK
E/A/D/B/T/Z: E
BEZ
:FEHL
E/A/D/B/T/Z: A
BEZ
:MODE
E/A/D/B/T/Z: E
:U
=MODE
:=
M
11.1
:UN
M
20.0
:SPB =M001
:R
M
20.0
:
:A
DB
2
:L
=SCHJ
:T
DL
4
:L
=WOTG
:T
DR
4
:L
=TAG
:T
DL
5
:L
=MON
:T
DR
5
:L
=JAHR
:T
DL
6
:L
=STD
:ON
=AMPM
:ON
=MODE
:SPB =VORM
:L
KH 0080
:OW
VORM :T
DR
6
:L
=MIN
:T
DL
7
:L
=SEK
:T
DR
7
:UN
M
11.2
:S
M
11.2
:L
KT 020.1
:SV
T
10
M001 :U
T
10
:BEB
EWA 4NEB 811 6130-01b
UHR STELLEN
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BI
BI/BY/W/D: BY
BI/BY/W/D: BY
BI/BY/W/D: BI
BI/BY/W/D: BI
24H-MODUS = 0, 12H-MODUS = 1
(UHRENMODUS STATUSWORT BIT 1)
MERKER IST RUECKGESETZT, WENN
STELLWERTE BEREITS IN DEN
UHRENDATENBEREICH EINGELE-
SEN WURDEN
UHRENDATENBEREICH
WERT FUER SCHALTJAHR ABLEGEN
WERT FUER WOCHENTAG ABLEGEN
WERT FUER TAG ABLEGEN
WERT FUER MONAT ABLEGEN
WERT FUER JAHR ABLEGEN
WERT FUER STUNDE ABLEGEN
WENN 12H-MODUS EINGESTELLT IST
UND AMPM-BIT = 1 (NACHMITTAGS),
DANN WIRD ENTSPRECHENDES BIT
IM UHRENDATENBEREICH
GESETZT
WERT FUER MINUTE ABLEGEN
WERT FUER SEKUNDE ABLEGEN
STELLWERTE UEBERNEHMEN
(STATUSWORT IST MW10)
UEBERWACHUNGSZEIT STARTEN
BEB, WENN UEBERWACHUNGSZEIT
NOCH NICHT ABGELAUFEN
Integrierte Uhr
Erläuterung
13-15