Parameterization and Configuration

6.3.3.15.1 Scaling: Measuring step

Alternatively, this parameter can also be set during operation via acyclic parameter access to the
scaling function PNU 65006, see page 139.
Function, if parameter Scaling: Total Measuring Range = 0:
The total number of steps over the whole measurement range of the measuring system is defined, via
the measuring length stored in the measuring system and the resolution set here.
Selection
Description
1000
Resolution = 1 µm per step
2000
Resolution = 2 µm per step
5000
Resolution = 5 µm per step
10 000
Resolution = 10 µm per step
50 000
Resolution = 50 µm per step
100 000
Resolution = 100 µm per step
1000 000
Resolution = 1 mm per step

6.3.3.15.2 Scaling: Total Measuring Range

Alternatively, this parameter can also be set during operation via acyclic parameter access to the
scaling function PNU 65007, see 139.
Function, if parameter Scaling: Total Measuring Range = 0:
The total number of steps over the whole measurement range of the measuring system is defined, via
the measuring length stored in the measuring system and the resolution set under the parameter
Scaling: Measuring step.
Function, if parameter Scaling: Total Measuring Range > 0:
The resolution of the measuring system is defined in [µm], via the measuring length stored in the
measuring system and the total number of steps over the whole measurement range set here. The
setting under the parameter Scaling: Measuring step is ignored in this case.
Data type
Unsigned32
Lower limit
0 steps
Upper limit
4 294 967 295 steps
Default
0 steps

6.3.3.16 Tolerated sign-of-life errors (V4.2)

Alternatively, this parameter can also be set during operation via acyclic parameter access to the
master sign-of-life error function PNU 925, see page 141.
The max. number of permissible errors of the master sign-of-life counter is defined with this
parameter. The parameter Compatibility Mode V3.1 must be set to disable for this purpose. If
the max. number of permissible errors is exceeded, the error code 0x0F02 is transmitted instead of
the position via signal G1_XIST2.
Data type
Unsigned8
Lower limit
0, Function is switched off
Upper limit
255
Default
1
 TR-Electronic GmbH 2018, All Rights Reserved
Page 126 of 168
TR-ELA-BA-DGB-0027 v09