8.3 Remote control
The remote control has a connection block at the rear, the block has six clamps which are to be connected
to the alarm control centre.
(+)
+12V/DC from clamp 10 on the alarm control centre
(-)
Ground from clamp 11 on the alarm control centre
CLOCK
Clock from clamp 12 on the alarm control centre
DATA
Data connection from clamp 13 on the alarm control
centre
N.C. TAMPER
NC-contact (NC = normally closed = opener = the
switching contact opens in the case of an alarm)
should be connected to a 24 hour loop from the alarm
control centre.
These clamps are connected with a sensor which
breaks the contact when the housing is opened.
8.4 Panic button
You can connect the panic button to the alarm control centre as an NC or NO contact. There are 3 clamps
on the back of the panic button for this purpose.
It is recommended that you connect the panic button to a 24 hour loop.
Use the COM connection either with NC or NO connection.
Common connection for NC and NO
COM
NC
This clamp is switched in series to the closure resistance.
This clamp is switched in parallel to the closure resistance.
NO
8.5 Magnet contact
The magnet contacts supplied have an NC contact, so they
must be switched in series to the closure resistance.
When the magnet contact is broken, this breaks the circuit
at the same time and the alarm control centre detects the
change in resistance.
103