Order number 6RM80..
Rated DC voltage
1)
Rated DC current
Auxiliaries power connection
Rated supply voltage
1)
Auxiliary supply
short-circuit current capability
Current demand
3)
Maximum permissible protection
on the customer's side
Maximum permissible protection
on the customer's side with option L85
Motor fan
Rated supply voltage
Setting range of the
motor circuit breaker
Cabinet cooling
Type of cooling
Fan air flow
Fan noise level
Cabinet
Frame size
(dimensions, see Chapter Design
(Page 22))
Weight without options (approx.)
Connection: Connection point, connection system, connection cross-section
for tightening torques, see tables.
1U1, 1V1, 1W1
AC armature without filter
1U1, 1V1, 1W1
AC armature with filter
1C1, 1D1
DC armature
3C, 3D
DC field without/with option L85
3-ph AC auxiliary supply with filter
without/with option L85
3-ph AC auxiliary supply without filter
without/with option L85
SINAMICS DCM Cabinet
Operating Instructions, 04/2015, A5E36161239/RS-AA/001
..88-6LV62
V
390
A
30
V
2-ph 480 V AC (+10 % / -20 %), 50 Hz
kA
50
A
A
63
A
-
3-ph 400 V AC, 50 Hz / 3-ph 460 V AC, 60 Hz
A
11 to 16
Device fan
m
/h 1000
3
dBA
66
DC
kg
600
Customer connections
Terminal end
4x120 mm², M12
Customer connections
4x120 mm², M12 6x120 mm², M12 6x185 mm², M12
SINAMICS DCM DC Converter
4x150 mm², M12 8x95 mm², M12
Terminal strip -X3
ST6, ST6-PE / -
4 mm²/-
Terminal strip -X1
ST35, ST35-PE /
-
16 mm²/-
Terminal strip -X1
ST35, ST35-PE /
-
16 mm²/-
10.3 Technical specifications
..93-4LV62
..95-4LV62
390
390
40
40
50
50
100
100
125
125
2 x (11 to 16)
2 x (11 to 16)
Device fan
Device fan
2400
2400
77
77
EC
EC
845
925
Terminal end
Terminal end
6x120 mm², M12
6x185 mm², M12
8x150 mm², M12
7)
7)
ST10, ST10-PE / UK35, USLKG35
6 mm²/25 mm²
6 mm²/25 mm²
UKH50, USLKG50 /
UKH50, USLKG50
35 mm²/50 mm²
35 mm²/50 mm²
UKH50, USLKG50 /
UKH50, USLKG50
35 mm²/50 mm²
35 mm²/50 mm²
Technical specifications
183