Electrical installation
4.10 Other connections
4.10.2
m.c.b. trip combined alarm signal
The signaling contacts of the circuit breakers and motor circuit breakers installed in the
control cabinet are combined in a notification chain and the resulting "No m.c.b. trip" signal to
terminals is provided floating.
Table 4- 9
Terminal
1
2
Max. connectable cross-section: 2.5 mm
When the combined alarm signal is activated, the system must be brought to a safe state in
(shutdown).
4.10.3
External E-STOP button
Terminals are available at which an external push button (form B contact) can be integrated
into the E-STOP circuit. This contact must be floating, since the electrical circuit is supplied
by a special safety voltage ES/P24 from the SINAMICS DCM DC Converter. These
connections can be omitted if option L57 (Emergency Off) or L59 (Emergency Stop) is
selected.
Table 4- 10
Terminal
3
4
Max. connectable cross-section: 2.5 mm
Note
The E-STOP function is not an EMERGENCY OFF function in the sense of EN 60204-1.
92
Terminal strip X2 - connection for m.c.b. trip combined alarm signal
CAUTION
Terminal strip X2 - connection for E-STOP button
Designation
-
-
2
Designation
-
-
2
Operating Instructions, 04/2015, A5E36161239/RS-AA/001
Technical data
Dry contacts for 24 V DC up to
max. 230 V AC
Technical data
Electrical circuit 24 V DC
ES/P24
SINAMICS DCM Cabinet