Commissioning
Explosion hazard due to incorrect installation!
Non-compliance results in severe or fatal injuries.
• Check the device for proper installation before commissioning.
• Comply with national regulations.
Damage or destruction of the device by arc and high pressure is
possible if improper switching operations are used!
Non-compliance can result in severe or fatal injuries.
• Quickly switch the device on and off completely.
• Avoid switching positions between 0 and I (ON and OFF).
Before commissioning, do the following:
• Check the mounting and installation.
• Enclosure must not be damaged.
• Remove any foreign bodies.
• If necessary, clean the connection chamber.
• Check if the conductors have been inserted correctly.
• Check whether all screws and nuts have been tightened firmly.
• Check whether all the cable entries and stopping plugs have been tightened firmly.
• Check whether all conductors have been clamped firmly.
• Observe the line voltage.
• Seal the unused cable entries with plugs certified according to
Directive 2014/34/EU or IEC and unused drilled holes with stopping plugs
certified according to Directive 2014/34/EU or IEC.
9
Operation
The wall-mounting socket may only be operated when fully mounted.
The wall-mounting socket can be switched only with the plug inserted.
If the plug has been disconnected, close the hinged cover with the
bayonet ring.
Only Type 8571/12 plugs from R. STAHL may be used.
276198 / 8571640300
2020-11-03·BA00·III·en·00
DANGER
WARNING
SolConeX Wall-Mounted Socket, 32 A
Series 8571/11
Commissioning