Herunterladen Inhalt Inhalt Diese Seite drucken

Grundfos MGE Serie Montage- Und Betriebsanleitung Seite 21

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 72
Terminal Type
NC
Normally closed contact
C1
Common
NO
Normally open contact
NC
Normally closed contact
C2
Common
NO
Normally open contact
18
GND
11
DI4/OC2
19
Pt100/1000 input 2
17
Pt100/1000 input 1
12
AO
9
GND
14
AI3
1
DI2
21
LiqTec sensor input 1
20
GND
22
LiqTec sensor input 2
10
DI3/OC1
4
AI1
OC
+24 V*
+24 V*
+24 V*/5 V*
+24 V*
OC
+24 V*
GND
+24 V*
+24 V*
+24 V*/5 V*
+24 V*
+24 V*
+24 V*/5 V*
Function
Signal relay 1. LIVE or PELV.
Signal relay 2. PELV only.
Protective earth.
Digital input/output, configurable.
Open collector: Maximum 24 V resistive or inductive.
Pt100/1000 sensor input
Pt100/1000 sensor input
Analog output:
0-20 mA or 4-20 mA
0-10 V.
Protective earth.
Analog input:
0-20 mA or 4-20 mA.
0.5 - 3.5 V, 0-5 V or 0-10 V.
Digital input, configurable.
LiqTec sensor input.
White conductor.
Protective earth.
Brown and black conductors.
LiqTec sensor input.
Blue conductor.
Digital input/output, configurable.
Open collector: Maximum 24 V resistive or inductive.
Analog input:
0-20 mA or 4-20 mA.
0.5 - 3.5 V, 0-5 V or 0-10 V.
NC
C1
NO
NC
C2
NO
18
GND
DI
11
DI4/OC2
19
Pt100/1000
17
Pt100/1000
12
AO
9
GND
+5 V*
14
AI3
1
DI2
21
LiqTec
20
GND
22
LiqTec
DI
10
DI3/OC1
4
AI1
2
DI1
+
+
5
+5 V
6
GND
A
GENIbus A
Y
GENIbus Y
B
GENIbus B
3
GND
15
+24 V
8
+24 V
26
+5 V
23
GND
25
GDS TX
24
GDS RX
+5 V*
7
AI2
21

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading