Application and function of the
analogue inputs AI1 ... AI4
Settings
Set control mode
Setting assistant, setpoints, options
Manual operation
Manual override
Twin-head pump operation
Set twin-head pump
External interfaces
Analogue, digital, SSM, SBM ...
Fig. 66: External interfaces
External interfaces
Function analogue input (AI1)
Differential pressure sensor, 2-10 V
Function analogue input (AI2)
Not configured, 0-10 V
Analogue input (AI3) function
Not configured, 0-10 V
Analogue input (AI4) function
Not configured, 0-10 V
Fig. 67: Function analogue input
198
Override function priorities
Priority*
1
2
3
4
Table 43: Override function priorities
* Priority 1 = highest priority
Key lock priorities
Priority*
1
2
3
Table 44: Key lock priorities
* Priority 1 = highest priority
Priorities for heating/cooling switchover using binary input
Priority*
1
2
Table 45: Priorities for heating/cooling switchover using binary input
* Priority 1 = highest priority
Analogue inputs can be used for setpoint input or actual value input. The allocation of set-
point and actual value specifications is freely configurable.
Settings 0-10 V, 4-
20 mA, PT1000, Ext. OFF,
Ext. MIN....
Use the menus "Analogue input AI1 function" ...  "Analogue input AI4 function" to set the
type of use (setpoint sensor, differential pressure sensor, external sensor, etc.), the signal
type (0 ... 10 V, 0 ... 20 mA, etc.) and the corresponding signal/value assignments. In addition,
information about the current settings can be queried.
The analogue input is pre-defined for the required signal depending on the selected control
mode of the pump.
In the "Settings" menu 
1.
"External interfaces"
2.
"Function analogue input AI1" ... "Function analogue input AI2".
Set the used signal type
and the associated
parameters for the
analogue input
.
Example: setting an external setpoint sensor for Δp-v
After selecting one of the options "Analogue input (AI1) function" ... "Analogue input (AI4)
function", select the following query or setting:
Installation and operating instructions • Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D • Ed.02/2022-07
Function
OFF, External OFF (binary input), External OFF (bus system)
MAX, External MAX (binary input), External MAX (bus system)
MIN, External MIN (binary input), External MIN (bus system)
MANUAL, External MANUAL (binary input)
Function
Key lock: digital input active
Key lock active via menu and buttons
Key lock: not active
Function
Cooling
Heating
, select
NOTICE
The differential pressure sensor of the Stratos GIGA2.0-I/-D is pre-con-
figured to 2 ... 10 V at the factory.
For the Stratos GIGA2.0-I/-D ... R1, no analogue input is configured at the
factory.