Versions with auxiliary contacts for intrinsically safe circuits:
Mounting the auxiliary contacts (option)
Danger caused by clearances and creepage distances being too short!
Do not operate the Ex i auxiliary contacts without attached cover!
The customer is only allowed to install an intrinsically safe auxiliary contact if no
read-off terminals are mounted on the two terminals located on the left and right side
of the respective mounting slot!
Before mounting an auxiliary contact, the cover must be removed.
X
The IP protection of the switch, IP20 (finger safe), remains active even if
the cover is removed.
The switching function of the auxiliary contact depends on the mounting
X
slot used (see chapter "Technical Data").
Carefully remove the cover (1) of the mounting slot (3) using a screwdriver.
Carefully insert the auxilary contact (2) into the mounting slot until it engages.
Paste the circuit diagram indicating the respective switching function to the rating plate
of the switch.