Technical Data
7
Technical Data
Explosion protection
Gas explosion protection
ATEX
IECEx
Dust explosion protection
ATEX
IECEx
Certificates
Europe (ATEX)
IECEx
Ambient temperature
Rated operational voltage
Rated operational current
Rated insulation voltage
Switching capacity
Short circuit protection
Without thermal protection
With thermal protection
4
SolConeX Switch Socket
8581/31
E II 2 G Ex d e IIC T6 (Ta = - 30 ...+ 40 °C)
E II 2 G Ex d e IIC T5 (Ta = - 30 ...+ 50 °C)
with intrinsically safe auxiliary contacts:
E II 2 G Ex d e [ib] IIC T6 (Ta = - 30 ...+ 40 °C)
E II 2 G Ex d e [ib] IIC T5 (Ta = - 30 ...+ 50 °C)
Ex d e IIC T6 (Ta = - 30 ...+ 40 °C)
Ex d e IIC T5 (Ta = - 30 ...+ 50 °C)
with intrinsically safe auxiliary contacts:
Ex d e [ib] IIC T6 (Ta = - 30 ...+ 40 °C)
Ex d e [ib] IIC T5 (Ta = - 30 ...+ 50 °C)
E II 2 D Ex tD A21 IP66 T65 °C (Ta = - 30 ... + 40 °C)
E II 2 D Ex tD A21 IP66 T75 °C (Ta = - 30 ... + 50 °C)
Ex tD A21 IP66 T65 °C (Ta = - 30 ... + 40 °C)
Ex tD A21 IP66 T75 °C (Ta = - 30 ... + 50 °C)
PTB 01 ATEX 1161
IECEx PTB 06.0034
see explosion protection data
- 45 °C on request (internal lubrication with silicone grease)
assignment of temperature class / ambient temperature / rated operational voltage /
rated connection cross-section
temperature class
T6
T5
( + 50 °C
( + 40 °C
( + 55 °C
( + 45 °C
( + 60 °C
( + 45 °C
( + 50 °C
( + 45 °C
( + 60 °C
max. 690 V
max. 125 A
max. 630 V
acc. to IEC/EN 60947-3, IEC/EN 60947-4:
AC-3
DC-23
690 V, 125 A
220 V, 125 A
120 V, 125 A
60 V, 125 A
1)
1 contact
2)
2 contacts connected in series
3)
3 contacts connected in series
125 A gG acc. to IEC/EN 60269-2
160 A gG acc. to IEC/EN 60269-2
rated operational
rated connection cross-section
current
socket / plug
125 A
70 / 50 mm
115 A
100 A
125 A
50 / 35 mm
70 / 35 mm
115 A
For the plug, a heat-resistant cable
100 A
) 85 °C, e.g. , NSSHÖU, must be used.
DC-1
3)
220 V, 125 A
2)
120 V, 125 A
1)
60 V, 125 A
2
2
2
3)
2)
1)
205582 / 8581615300