0x06 - "Get Fro-
Available for:
nius Solar Net
up to 100 inverters
status"
via RS 232
X
The "0x06 - Get Fronius Solar Net status" command displays the current network status of
the interface card / interface box / interface unit of the Datalogger & interface.
The network status of interface card / interface box / interface unit of Datalogger & interface
is output as an "unsigned" character data type with 1 byte.
One possible cause of an error message when querying the network status is an open net-
work ring. The cause of an open network ring may be a defective network cable or a miss-
ing termination plug.
An open network ring is indicated on the Datenlogger by the red LED lighting up.
Query:
Start Length Device / Op-
Response:
Start Length Device / Op-
0x9F - "Set power
Using the "0x9F - Set power reduction and reactive power" command, the relevant inverter
reduction and re-
can be set to a remote control mode to activate effective power reduction and/or a reactive
active power"
power specification from a third party device.
(general descrip-
-
tion of command)
-
-
172
1 inverter via RS
232
(IFC easy)
-
NOTE! The "Get Fronius Solar Net status" command displays the current network
status of only the interface card / interface box / interface unit of the Datalogger &
interface, not of the complete system.
tion
0x00
0x00
tion
0x01
0x00
When a command is sent regarding reactive power, the relevant inverter continues us-
ing the reactive power specification last received for 60 seconds in remote control
mode.
NOTE! To maintain the remote control mode for a command regarding reactive
power for longer periods of time, the relevant command should be sent cyclically
at intervals of at most 60 seconds.
For Fronius IG Plus and Fronius CL only:
When a command is sent regarding effective power, the relevant inverter continues
using the effective power specification last received until the next DC disconnector in
remote control mode.
For Fronius IG-TL and Fronius Agilo only:
When a command is sent regarding effective power, the relevant inverter continues
using the effective power specification last received until the next AC disconnector in
remote control mode.
up to 100 inverters
via RS 422
(IG Plus/CL)
-
Number
Com-
Check-
mand
sum
0x06
Number
Com-
Solar Net status
mand
0x06
(1 Byte
1 = Fronius Solar
Net OK
0 = Fronius Solar
Net Error)
up to 100 inverters
via RS 422 (IG-TL,
Agilo)
-
Check-
sum