Water-cooled
converter
Rated input voltage 3 AC 380 to 480
6SE7021-3EB 1-1AA1
6SE7021-8EB 1-1AA1
6SE7022-6EC 1-1AA1
6SE7023-4EC 1-1AA1
6SE7023-8ED 1-1AA1
6SE7024-7ED 1-1AA1
6SE7026-0ED 1-1AA1
6SE7027-2ED 1-1AA1
NOTE
Siemens AG
SIMOVERT MASTERDRIVES
Downloaded from
www.Manualslib.com
Order No.
Power loss
(at 2.5 kHz)
[kW]
0.21
0.16
0.33
0.47
0.58
0.71
0.86
1.07
= 5 corresponds to MASTERDRIVES Motion Control
= 7 corresponds to MASTERDRIVES Motion Control Performance 2
Table 11-5
These units and the air-cooled converters are identically constructed.
Instead of the heat sink for air, an air/water cooler has been installed.
All the technical data not listed in Table 11-5 for a particular unit are the
same as those of the air-cooled converter. The first 12 positions of the
Order No. are identical. The supplement "-1AA1" indicates water
cooling.
*)
The cooling water requirement applies for the unit rating of the converter and 100%
utilization of the additional heat dissipation obtained from a water temperature rise
intake/return of ∆T = 5 K.
Siemens Controls
6SE7087-6JD50
Operating Instructions
manuals search engine
Cooling-
Maximum
water
additional heat-
require-
dissipation power
*)
at Tair ≤ 30 °C
ment
[l/min]
[kW]
1.00
0.1
1.20
0.1
2.10
0.2
2.60
0.2
4.25
0.5
4.80
0.5
5.25
0.5
6.00
0.5
Water-cooled converter
Technical Data
Typical pressure drop
according to volumetric flow
0.15 to 0.2 bar at 1.2 l/min
0.15 to 0.2 bar at 1.2 l/min
0.15 to 0.2 bar at 2.6 l/min
0.15 to 0.2 bar at 2.6 l/min
0.15 to 0.2 bar at 6.0 l/min
0.15 to 0.2 bar at 6.0 l/min
0.15 to 0.2 bar at 6.0 l/min
0.15 to 0.2 bar at 6.0 l/min
11-7