Herunterladen Inhalt Inhalt Diese Seite drucken

Siemens SIMOVERT MASTERDRIVES Betriebsanleitung Seite 198

Vorschau ausblenden Andere Handbücher für SIMOVERT MASTERDRIVES:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Connecting-up
X101 - Control
terminal strip
WARNING
NOTE
7-10
Downloaded from
www.Manualslib.com
The following connections are provided on the control terminal strip:
♦ 4 optionally parameterizable digital inputs and outputs
♦ 2 digital inputs
♦ 1 analog input
♦ 1 analog output
♦ 24 V aux. voltage supply (max. 150
and outputs
If the digital inputs are supplied from an external 24 V supply, this must
be referenced to frame X101.2. Terminal X101.1 (P24 AUX) may not
be connected with the 24V supply.
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
Connectable cross-section: 0.14 mm
Terminal 1 is at the top when installed.
Table 7-6
In the case of digital inputs, levels below 3 V are interpreted as low and
levels above 13 V as high.
The outputs of the customer terminal can assume undefined states
during power up/board initialization/execution time overflow, unless a
specific response has been expressly defined (and implemented in the
hardware) for these periods.
manuals search engine
mA,
Designation
Meaning
P24 AUX
Aux. voltage supply
M24 AUX
Reference potential
DIO1
Digital input/output 1
DIO2
Digital input/output 2
DIO3
Digital input/output 3
DIO4
Digital input/output 4
DI5
Digital input 5
DI6
Digital input 6
Analog input +
AI+
Analog input −
AI−
AO
Analog output
M AO
Ground analog output
2
to 1.5 mm
Control terminal strip
Operating Instructions
08.2009
output only!) for the inputs
Range
DC 24 V / 150 mA
0 V
24 V, 10 mA / 20 mA
24 V, 10 mA / 20 mA
24 V, 10 mA / 20 mA
24 V, 10 mA / 20 mA
24 V, 10 mA
24 V, 10 mA
11 bit + sign
differential input:
± 10 V / Ri = 40 k
8 bit + sign
± 10 V, 5 mA
2
(AWG 16)
6SE7087-6JD50
Siemens AG
SIMOVERT MASTERDRIVES

Quicklinks ausblenden: