Herunterladen Inhalt Inhalt Diese Seite drucken

Water Connections - RHOSS WinPACK HE-A SE TCAEY 2150 Handbuch

Kompakte luftgekühlte kaltwassersätze und wärmepumpen, umschaltbar, mit umweltfreundlichen kältemittel r410a. baureihe mit hermetischen scroll-verdichtern
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

WATER CONNECTIONS

Connection to the system
IMPORTANT!
The layout of the water system and connection of the system to the unit must be
carried out in conformity with local and national rules in force.
IMPORTANT!
We recommend installing isolating valves that isolate the unit from the rest of the
time to time.
The unit is designed for outdoor installation.
The unit is provided with Victaulic type hydraulic connections on the
water inlet and outlet of the air conditioning system.
The unit should be positioned to comply with the minimum recommen-
ded clearances, bearing in mind the access to water and electrical
connections.
The unit can be equipped with anti-vibration mounts upon request
(SAG/SAM).
Shut-off valves must be installed that isolate the unit from the rest of
the system. Elastic connection joints and system/machine drain taps
MUM/MINIMUM values indicated in the
Correct installation and positioning includes levelling the unit on a sur-
face capable of bearing its weight.
During long periods of inactivity, it is advisable to drain the water from
the system.
It is possible to avoid draining the water by adding ethylene glycol to
the water circuit (see "Use of antifreeze solutions").
The size of the expansion tank must be calculated by the installer
depending on the system. In the case of models without a pump, the
It is advisable to install an air bleed valve.
Once the connections to the unit are made, check that none of the
pipes leak, and bleed the air from the system.
Installation and management of utility pump outside of unit
The circulation pump to be installed in the main water circuit should
be selected to overcome any pressure drops, at nominal rates of
user pump operation must be subordinated to the machine operation;
the microprocessor controller runs the control and management of
the pump according to the following logic: upon the machine ignition
has priority over the rest of the system. During the start-up phase, the
temporarily excluded, for a preset period, in order to avoid oscillations
caused by air bubbles or turbulence in the water circuit. After this time,
on working all the time the unit is in operation, and it shuts down only
at the switch-off command. After switch-off, the pump will continue to
the residual heat in the water exchanger
See also section attachment "hydraulic circuits".
Section II :: Installation and maintenance
-
section.
79
EN

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis