Maintenance and troubleshooting
11.3.

If you encounter problems

Red
Current
Transistor
LED
output
output
ON
22 mA
1)
depending
on thresh-
olds
ON
22 mA
1)
depending
on thresh-
olds
ON
22 mA
1)
depending
on thresh-
olds
ON
22 mA
1)
depending
on thresh-
olds
Icon
Message displayed
in the Info menu
"No sensor board"
ERR
+
"TR EE Fact Read"
ERR
+
"TR EE User Read"
"TR EE UserWrite"
ERR
+
"E:Frequency"
ERR
+
Meaning
What to do
The link to the measure-
ment module is interrupted
Parameter reading error
Parameter saving error
The input frequency is out
of range.
This message is displayed
if monitoring of the input
frequency is activated,
depending on the pro-
grammed thresholds ERR
LO and ERR HI).
Switch the power supply off then on again
if the error persists, return the device to Bürk-
ert
Switch the power supply off then on again
if the error persists, set the device back to the
default settings
if the error persists, return the device to Bürk-
ert
Switch the power supply off then on again,
save the parameters again
if the error persists, set the device back to the
default settings
if the error persists, return the device to Bürk-
ert
Go into the "Sensor" function in the Diag-
nostic menu to read the value of the input
frequency
check that the paddle is clean and that it ro-
tates freely on its axis or
check that the oval gears rotate freely.
check the installation.
english
29