11.5.
in the event of problems,
excluding calibration
Red led
4-20 mA
meaning
status
output
status
flashing
4-20 mA Fluid temperature
(once a
outside the
second)
operating range
(-20...100°C).
on
22 mA
Connection with
temperature
probe interrupted
34
Resolution
→
Check the fluid
temperature.
→
Return the fluid tem-
perature to within
the operating range
(-20...100°C).
→
Power off the device.
→
Power the device on.
→
If the fault persists,
contact your Bürkert
retailer.
Type 8222 ELEMENT neutrino
Sparepartsandaccessories
12.
spARE pARTs ANd
AccEssoRiEs
Caution
Risk of injury and/or damage caused by the use of unsuitable
parts.
Incorrect accessories and unsuitable replacement parts may
cause injuries and damage the device and the surrounding area.
•
Use only original accessories and original replacement parts
from Bürkert.
Spare part
Seal in EPDM for the threaded sensor
Seal in EPDM for cover / box tightness
Accessories
M12, 5-pin female connector, to be wired
M12, 5-pin female connector, moulded on
shielded cable (2 m)
Calibration solution, 500 ml, 5 µS
Calibration solution, 500 ml, 15 µS
Calibration solution, 500 ml, 100 µS
Calibration solution, 500 ml, 706 µS
Calibration solution, 500 ml, 1413 µS
english
Order code
561955
561752
Order code
917116
438680
440015
440016
440017
440018
440019