1.3.2 Fitting outdoors (OD)
OD type ventilators are designed for
outdoor use and can be used for
transport of air in the temperature range
up to 200°C. This version is also fitted
with a drain in installation method "A"
A and B fitting methods should be
used for outdoor fitting. Fitting
methods C and D require a specially
designed ventilator (Fig. 4) — contact
EXHAUSTO.
All exterior seams, including spigots
have been jointed to prevent water from
getting inside.
The cabinet is class C4 DS/EN ISO12
944.2 certified and designed for
outdoors.
Service access
Wherever the ventilator is fitted, there should
be space enough to be able to open the
service door to an angle of approx. 80° and to
access the locking screws.
1.3.3 Fitting the mounting bars
•
Mounting should be done on a stable vibration-resistant base, to minimise any
vibration that might be caused by the ventilator. A cement slab placed on a
wooden base construction is recommended.
•
Fit the mounting bars on the cabinet with the supplied fitting screws. The cabinet
has holes already bored for fitting method A.
•
BESB 400 and 500: When using fitting method B (Fig. 2/4) for BESB 400 and
500, holes (Ø16 - Ø20) are bored in the cabinet for the fitting of the mounting
bars.
•
Fit the mounting bars while the ventilator is on the pallet.
•
Sit the ventilator on the supporting base. Do not fasten the ventilator to the base.
A
B
Fig. 4
6/64
GB - BESB – Product information
C
D
D
D
Fig. 6
Fig. 5