6.4 Safety zone for floor level
installation
If the device is installed at floor level, a safety zone
ters must be observed all the way around the device. There
must not be any ignition sources such as sockets, light
switches, lamps, electrical switches or other permanent ignition
sources, windows doors, ventilation openings, light wells, drain-
age openings and similar in this zone. Fire loads must also be
2000
Fig. 6.4:Safety zone (floor level installation) around the heat pump
EN-12
of 2 me-
1
825
2000
1
2
800
452171.66.01-EN · FD 0212
avoided. Open drains to a lower level are permitted providing
there are no openings into the sewer system within 2 metre
around them. Building openings must be made airtight within
the safety zone. The safety zone must not protrude onto neigh-
bouring property or public traffic areas. The device must be po-
sitioned so that in the event of a leakage no refrigerant can get
into neighbouring buildings.
No structural modifications are to be made in the safety zone
that could violate the integrity of the safety zone.
825
1420
2000
LA 1118CP
2000
www.dimplex.de