5-3. Settings of Counter Modules Sold
Separately
For the counter module, the module address and the count polarity
and resolution of the measuring unit to be connected are set by
using switches.
For further details, refer to the operating instructions of the counter
module.
5-3-1. Counter Module Number (Channel
Number) Setting Switch
This switch is used to set the module number to a number from 0 to
F.
Module numbers are used to designate the channel number of the
measuring unit in the commands which are input for the settings
and operations.
Do not use the same number for more than one module in the same
unit.
Setting the same number for more than one module will prevent
the system from operating properly.
20
(E)
5-3-2. Measuring Unit Settings
Set the measuring unit setting switches to suit the measuring unit
to be connected.
For further details, refer to the operating instructions of the counter
module concerned.
Count polarity setting
Push-in direction "+"
Push-in direction "_"
Bold print is used to indicate the factory settings.
Sensor supported
SW 2
—
OFF
DK series (0.1 um) ON
DK series (0.5 um) OFF
DG**B series
DT512
ON
DT12, DT32,
OFF
DL**BR
DL310B, DL330B
ON
—
OFF
—
ON
SW 1
ON
OFF
SW 3
SW 4
Resolution
OFF
OFF
Not used
OFF
OFF
0.1 um
ON
OFF
0.5 um
ON
OFF
1 um
OFF
ON
5 um
OFF
ON
10 um
ON
ON
Not used
ON
ON
Not used
MG10-P1 / MG10-P2