Herunterladen Inhalt Inhalt Diese Seite drucken

Balluff BOS R254K-UUI-LK10-S4 Konfigurationsanleitung Seite 158

Vorschau ausblenden Andere Handbücher für BOS R254K-UUI-LK10-S4:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

BOS R254K-UUI-LK10-S4
Photoelectric Sensors
5
Primary Device Functions (continued)
5.8.3
ISDU
Name
Mode
0x009E
Alarm Threshold
Current Receiver
0x005D
Level
Tab. 5-29: Automatic Switching Threshold Adaption – ISDU
Mode
Value
Name
0x00 (0)
Deactivated
0x01 (1)
Activated
Tab. 5-30: Automatic Switching Threshold Adaption – Mode
Alarm Threshold
An Alarm Threshold can be set for soiling detection. The
value range is 20%...90%. If the light reception level
normalized to the 100% reference falls below the alarm
threshold, the event Maintenance Required – Cleaning is
output and the Device Status is also set to 1 –
Maintenance Required. In this case, the front lens of the
sensor or the reflector should be cleaned.
Current Receiver Level
The Current Receiver Level parameter is used to output
the currently available reception level to the reflector,
referenced against the 100% reference. The parameter is
thus a value for the current degree of soiling of the sensor.
If no valid measurement value is available after switching
on the sensor, the value of 255 is read out.
5.8.4
Events
Event Code
Event Type
0x8C40
Warning
(35904)
Tab. 5-31: Automatic Switching Threshold Adaption – Events
46
english
Index
Subindex
Access
1
R/W
(158)
2
R/W
0
(93)
Description
The function is switched off
The function is switched on
Description
Maintenance required – Cleaning
► Clean the front lens of the sensor or reflector.
Length
Data Type
1 byte
ENUM
1 byte
UINT8
R
1 byte
UINT8
Data
Default
Storage
No
0x00 (0)
No
0x1E (30)
No
Device Status
1 – Maintenance-Required

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis