System functions

7.1
Device Status and Detailed Device Status
7.1.1
Description
The Device Status feature provides information about the
current device status.
Each Device Status is combined with a corresponding
diagnostic message (Events see chapter 3.6 on page
26).
It also makes it possible to actively read out currently
pending events of the device.
7.1.2
Process Data
Object ID
Name
0x002F (47)
System Error
Tab. 7-1:
Device Status and detailed Device Status – Process Data
Also see section Process Data Profiles on page 10.
7.1.3
ISDU
Name
Device Status
Detailed Device Status
Tab. 7-2:
Device status and detailed device status – ISDU
7.1.4
Device Status
The parameters are accessed via subindex 0. The output
values are to be interpreted as follows:
Value
Status
0
Device is operating properly.
1
Maintenance Required
2
Out-of-Specification
3
Functional check
4
Failure
Tab. 7-3:
Device Status
88
english
Description
This bit is set (TRUE) if there is an error in the device. This information is
linked to the device status (4-Failure), which can be triggered by different
device functions or diagnostic messages. The bit is reset as soon as the
error status no longer exists (FALSE).
Index
Subindex
Access
0x0024 (36)
0
0x0025 (37)
0
Description
Device working correctly.
Although the process data is valid, internal diagnoses show that the device will
soon lose its ability to function properly. Maintenance is necessary.
Although the process data is valid, internal diagnoses show that the device is
operating outside of its specified measurement range or environmental conditions.
The installation must be checked for unintentional malfunctions.
Process data is temporarily invalid due to intentional changes to the device, e.g.,
parameterization or teaching-in.
Process data is invalid due to a malfunction of the device or its peripheral devices.
The device is not able to perform its intended function. Re-configuration (resetting
to factory settings) can help. Otherwise, Balluff service must be contacted or the
device replaced.
Length
Data Type
R
1 byte
UINT8
R
30 bytes
UINT8[]
Direction
Input
Data Storage
Default
n/a
n/a
0x00 0x00
... 0x00