BNI CIP-351-000-K015
Safe I/O Module, EtherNet/IP™ CIP Safety™
IP67 Module
5. Product Characteristics
5.1.
Hardware characteristics
Type
Product Reference
Safety
SIL (per IEC 61508 /
IEC 62061)
CAT (per ISO 13849-1)
PL (per ISO 13849-1)
PFH
PFDavg
DCavg
MTTF
Service Life
Power
Power IN connector
Power OUT connector
Module & Input power (UB)
Operating current (UB)
Output power (UL)
Operating current (UL)
Safe Inputs
Channels
Connector
Input type
Input voltage
On / Off delay
Warning!
If
UB
is over 36 V for a period of 2 seconds or more. The safety module will go in fail
state (all LEDs are blinking in red) and considered as destroyed. Indeed, the internal
surge protections are irreversibly damaged and therefore the module cannot operate
anymore.
www.balluff.com
12x Safe Inputs + 4x Safe Outputs
BNI CIP-351-000-K015
Up to SIL3 (when configured in dual I/O Channel)
Up to Cat. 4 (when configured in dual I/O Channel)
Up to PL e (when configured in dual I/O Channel)
Mini Change (7/8"), 4-pin male, stainless steel, shielded, Maximum 8 A
Mini Change (7/8"), 4-pin female, stainless steel, shielded, Maximum 8 A
24 VDC, -15% / +20% (protected against power crossing).
24 VDC, -15% / +20% (protected against power crossing)
M12 Ultra-Lock, 5-pin, female, A-Coded, stainless steel, unshielded
Configurable from 0 to 1000ms (0 by default)
4.95 × 10
/h
-9
4.30 × 10
-4
96.32%
105 years
20 Years
<100 mA
<20 mA (without load)
12 channels
IEC61131-2 type 3
UB
(*)
35