Voltage measurement at external earthed socket
Measurement range
5 V - 270 V/AC
Displays:
Voltage between the external conductor (L) and the neutral conductor (N)
Voltage between the external conductor (L) and the protective conductor (PE)
Voltage between the neutral conductor (N) and the protective conductor (PE)
Limit values in accordance with DIN VDE 0701-0702 and ÖVE/ÖNORM E 8701-1
The limit values in bold are stored in the GT-6000
Protective conductor
resistance R
PE
Insulation resistance R
Protective conductor cur-
rent I
/I
EA
LEAK
Contact current I
/I
EA
LEAK
Never exceed the maximum permitted input values. Never touch circuits or parts of circuits when
they may contain voltages greater than 33 V/ACrms or 70 V/DC! Danger of death!
Resolution
1 V
Protection class 1
For leads with a rated current
≤16 A:
≤0.3 Ω (up to 5 m length)
+0.1 Ω (each additional 7.5 m)
max. 1 Ω
For leads with higher rated
currents, the calculated ohmic
resistance value applies
≥1 MΩ
ISO
≥2 MΩ for proof of safe isola-
tion (transformer)
≥0.3 MΩ for devices with
heating elements
≤3.5 mA
On conductive parts with PE
connection
1 mA/kW for devices with
heating elements P > 3.5 kW
≤0.5 mA
On conductive parts without
PE connection
Accuracy
±(5% + 2)
Protection class 2, 3
≥2 MΩ
(protection class 2)
≥ 0.25 MΩ
(protection class 3)
≤0.5 mA
On conductive parts
without PE connection
Lead test
≤0.3 Ω
(see protection class 1)
≥1 MΩ
71