R911172834 / 02
|
PRC7000
7.2.5
24V
logic supply (XDS1, input)
DC
Connection:
to XDS1,14-pole,
2 rows
Mating connector is comprised in the delivery.
Cable length:
(from power source to consumer)
max. 10 m at 0.75 mm
max. 75 m at 1.5 mm
Cable type:
unshielded, VDE 0281, 0812
The control logic must be supplied with 24 V
PRC7000
XDS1
1
2
Fig. 50: Logic supply input of the timer
Options:
• Supply via an external power supply unit.
"
Any external voltage sources used must be designed according to
the principles of "safety separation" (for example PELV) in ac
cordance with the Low-Voltage Directive (2006/95/EC).
Bosch Rexroth AG
2
2
.
DC
24V
DC
Power infeed for power supply
0V
to the internal control logic
273 / 334