Set the acceleration time T
(C0012)
Lenze setting: 5.00 s
11.
Set the deceleration time T
(C0013)
Lenze setting: 5.00 s
12.
Set the V/f-rated frequency
(C0015)
Lenze setting: 50.00 Hz
13.
Set the V
min
Lenze setting: Depends on the
controller type
14.
If you want to change other
settings, please go to the
menu
15.
Go to the
ALL
A Check the fan monitoring
setting under code C0608:
– for 8200 motec 0.25...0.37
kW and 0.55...2.2 kW:
C0608 = 0! (default setting)
– for 8200 motec 3...7.5 kW:
C0608 =1 (recommended)
or C0608 = 2!
Stop!
Function must be
activated during
commissioning!
Otherwise, the
controller may be
destroyed through
overheating!
– for all other controllers:
C0608 = 0 ! (default
setting)
B Select additional functions via
codes, if necessary.
When all settings are complete:
16.
Select the setpoint
17.
Enable the controller
18.
The drive should now be running.
L
Linear V/f-characteristic control
ir
f [ H z ]
C 0 0 1 1
f 2
f 1
if
boost (C0016)
Activate e.g. JOG frequencies
(C0037, C0038, C0039) or motor
ALL
temperature monitoring (C0119)
menu
E.g. via potentiometer at
terminals 7, 8, 9
EDK82MV222 DE/EN/FR 9.0
Commissioning
0
t i r
t i f
T i r
T i f
s
çìí
NMMB
s
ãáå
M
M
`MMNR
X3
20
28
T
= t
ir
ir
t
= acceleration time
ir
wanted
T
= t
if
if
t
t
= deceleration time
if
wanted
The Lenze setting is
suitable for all common
applications
Ñ
Terminal X3/28 = HIGH
misc002
If the drive does not
start, press  in
addition
T
C0011
f 2 − f 1
C0011
f 2 − f 1
NNP