Herunterladen Diese Seite drucken

Grundfos Multilift M Montage- Und Betriebsanleitung Seite 11

Vorschau ausblenden Andere Handbücher für Multilift M:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 79
5.2.3 Internal layout of LC 221
Figure
10
shows the internal layout of LC 221.
X5
Fig. 10 Internal layout of LC 221 (three-phase PCB as example)
Pos. Description
1
Terminals for power supply
2
Terminals for connecting pump 1
3
Terminals for thermal switch, pump 1
4
Terminals for external reset
5
Terminals for external alarm (outside the tank)
6
Terminals for common fault
7
Terminals for high-level alarm
8
Terminals for failure, pump 1
9
Terminals for operation, pump 1
Terminals for level switches (optional)
10
Terminals for additional high-level alarm (inside the tank)
11
Terminals for analogue sensor
12
Service connector to PC Tool
13
Connector for GENIbus interface module
14
Control circuit fuse
15
Piezoresistive pressure sensor module
16
DIP switches
17
Connector for battery, 9 V
Note: Cable connections for pos. 6-11:
Use a cable tie if leads protrude more than
20 mm from the cable sheath.
Comments
230 V
230 V
Potential-free changeover NO/NC
contacts with max. 250 V / 2 A.
Attention: Connect these terminals
to supply network potential or low
voltage, but do not mix the two.
Digital
Digital
0-5 V or 4-20 mA
Not in use for this application
Fine-wire fuse:
100 mAT / 20 mm x ∅5
0-5 V
Not in use for this application
Non-rechargeable batteries only.
The controller is not equipped with
a charging device.
Terminal designation
PE, N, L3, L2, L1
PE, N, W1, V1, U1
T1, T2
11, 12
13, 14
X11
X10
X8
X6
81-88
81, 82
91 (GND), 92 (signal), 93 (12 V)
-
-
-
-
-
-
11

Werbung

loading