8024871/06.06.2019 | SICK
Irrtümer und Änderungen vorbehalten
Befehl
HTTP-
Method
e
api/crown/ac/
POST
GetPortStatus
(lesen)
api/crown/ac/
POST
GetPortConfigura‐
(lesen)
tion
api/crown/ac/
POST
TriggerDataSto‐
(schrei‐
rage
ben)
api/crown/ac/
POST
FindMe
(schrei‐
ben)
api/crown/ac/
POST
GetRestDataIn‐
(lesen)
Length
SIG200-PARAMETRIERUNG
JSON-Anforde‐
JSON-Antwortteil Funktion
rungsteil
{ "data": {"Port":
{
1}}
"header": {
"status": 0,
"message": "Ok"
},
"data": {
"Status": "OK",
"Pin4Value":
false,
"Pin2Value":
false,
"ConnectedDe‐
vice": "PAC50-
BCD"
}}
{ "data": {"Port":
{
1}}
"header": {
"status": 0,
"message": "Ok"
},
"data": {
"Status": "OK",
"Pin4Configura‐
tion": "IOLink",
"PortOwner":
"Logic Editor",
"CycleTime": "as
fast as possible",
"IODDFileName":
"none",
"DataStorageLe‐
vel": "Disabled",
"VendorID": "0",
"DeviceID": "0"
}
{ "data": {"Port":
{
1}}
"header": {
"status": 0,
"message": "Ok"
},
"data": {
"Status": "No
Error"
}
{ "data":
-
{"Start":true}}
-
{
"header": {
"status": 0,
"message": "Ok"
},
"data": {"Value":
3}
B E T R I E B S A N L E I T U N G | Sensor Integration Gateway – SIG200
7
Gibt den Signalstatus und
Namen des angeschlosse‐
nen Geräts an einem IO-
Link-Port zurück („Port" =
1, 2, 3 oder 4).
Gibt die vollständige Port‐
parametrierung eines IO-
Link-Ports zurück („Port" =
1, 2, 3 oder 4).
Startet IO-Link „Data Sto‐
rage" (Datenspeicher), wie
für einen IO-Link-Port konfi‐
guriert („Port" = 1, 2, 3
oder 4).
Aktiviert das Blinken der
LED am SIG200 zur Identi‐
fizierung („Start" = „true"
oder „false").
Gibt die Menge der verfüg‐
baren Datenwerte für den
Zugriff auf Logikeditor-Ein‐
gänge zurück.
37