9.
as inTerface insTallaTiOn
9.1.
as interface connection
AS interface (Actuator Sensor Interface) is a field bus system which is used primarily for networking binary sensors
and actuators (slaves) with a higher-level control (master).
Bus line
Unshielded two-wire line (AS interface line as AS interface cable harness) along which both information (data) and
energy (power supply for the actuators and sensors) are transmitted.
network topology
Freely selectable within wide limits, i.e. star, tree and line networks are possible. Further details describe the AS
interface specification (A/B slave model conforms to the version 3.0 specification).
9.2.
Technical data for as interface pcBs
Supply:
via AS interface (29,5 V ... 31,6 V)
Outputs:
1 valve Y1, max. 1 W, power reduction after approx. 100 ms
with integrated Watch Dog function
Certification:
Licence no. 77601 according to version 3.0
9.3.
programming data
I/O configuration
ID code
Extended ID code 1
Extended ID code 2
Profile
Table 5:
Programming data
Bit configuration
data bit
Input
Output
parameter bit
Output
Table 6:
Bit configuration
32
B hex
A hex (see below for bit configuration)
7 hex
E hex
S-B.A.E
d3
d2
0 Top not reached
0 Bot not reached
1 Top reached
1 Bot reached
–
–
p3
p2
not used
not used
english
Type 8691
AS Interface Installation
d1
d0
–
–
0 Solenoid valve OFF
not used
1 Solenoid valve ON
p1
p0
"0" START Teach function
not used
"1" STOP Teach function