Herunterladen Inhalt Inhalt Diese Seite drucken

As-Interface Installation; As-Interface Connection; Technical Data For As-Interface Pcbs; Programming Data - bürkert 8691 Bedienungsanleitung

Steuerkopf
Vorschau ausblenden Andere Handbücher für 8691:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

10
as-inTerface insTallaTiOn
10.1
as-interface connection
AS-Interface (Actuator Sensor Interface) is a field bus system which is used primarily for networking binary sensors
and actuators (slaves) with a higher-level control (master).
Bus line
Unshielded two-wire line (AS-Interface line as AS-Interface cable harness) along which both information (data) and
energy (supply voltage for the actuators and sensors) are transmitted.
network topology
Freely selectable within wide limits, i.e. star, tree and line networks are possible. Further details describe the AS-
Interface specification (A/B slave model conforms to the version 3.0 specification).
10.2
Technical data for as-interface pcBs
Supply:
via AS-Interface (29,5 V – 31,6 V)
Outputs:
1 valve Y1, max. 1 W, power reduction after approx. 100 ms
with integrated Watch Dog function
Certification:
Licence no. 77601 according to version 3.0
10.3
programming data
I/O configuration
ID code
Extended ID code 1
Extended ID code 2
Profile
Table 6:

Programming data

Bit configuration
Data bit
Input
Output
parameter bit
Output
Table 7:
Bit configuration
36
D3
D2
0 Top not reached
0 Bot not reached
1 Top reached
1 Bot reached
p3
p2
not used
not used
english
aS-interface
31 slaves
B hex (1 input, 2 outputs)
F hex
F hex
F hex
S-B.F.F
D1
not used
p1
not used
Type 8691
AS-Interfaceinstallation
aS-interface
62 slaves
A hex
7 hex
E hex
S-B.A.E
D0
0 Pilot valve
OFF
1 Pilot valve
ON
p0
"0" START teach function
"1" STOP teach function

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis