6.3.1 Setting in connection with pump
replacement
If an uncontrolled pump is to be replaced with a UPE
Series 2000, settings can be made according to the
tables below.
Existing pump at maximum speed
Existing
UPE Series 2000
pump
Maximum
Setting of
head
head [m]
[m]
3
2
4
2
5
2.5
6
3
7
3.5
8
4
9
4.5
10
5
11
5.5
12
6
Read the tables as follows:
• If the maximum head of the existing pump is 6 me-
tres and the pump is running at maximum speed
under normal operating conditions, it is recom-
mended to set the UPED pump to 3 metres and to
select proportional pressure.
• If, however, the existing pump is running at a re-
duced speed, it is recommended to set the UPED
pump to 2 metres and to select constant pressure.
6.4 Max. or min. curve duty
Can be set by means of the control panel or the
R100.
The pump can be set to operate according to the
max. or min. curve, like an uncontrolled pump, see
fig. 9.
Fig. 9
H
Max.
Min.
10
Existing
pump
Maximum
Setting of
head
control mode
Constant pressure
Constant pressure
Proportional pressure
Proportional pressure
Proportional pressure
Proportional pressure
Proportional pressure
Proportional pressure
Proportional pressure
Proportional pressure
The max. curve mode can be selected if an uncon-
trolled pump is required. In this operating mode, the
pump will operate independently of an external con-
troller, if installed.
The min. curve mode can be used in periods in
which a minimum flow is required. This operating
mode is suitable for night-time duty.
Two different min. curves can be set by means of the
R100.
6.5 Constant curve duty
Can be set by means of the R100.
The pump can be set to operate according to a con-
stant curve, like an uncontrolled pump. Select one of
19 curves between the max. and min. curves, see
fig. 10.
Fig. 10
Q
Existing pump at reduced speed
UPE Series 2000
Setting of
head [m]
[m]
3
1.5
Constant pressure
4
1.5
Constant pressure
5
2
Constant pressure
6
2
Constant pressure
7
2.5
Proportional pressure
8
3
Proportional pressure
9
3.5
Proportional pressure
10
3.5
Proportional pressure
11
4
Proportional pressure
12
4
Proportional pressure
H
Max.
Min.
Setting of
control mode
Q